10471 Murrelektronik

MEF EMC-FILTER 1-PHASE 2-STAGE; Operating voltage : max. 250 V AC/300 V DC; Operating frequency : 50...60 Hz; Consumption : max. 5 mA (250 V AC); Overload current : 18× (IN t) max. 0.5 ms; 1.5× (IN t) max. 1 min. (1× per hour); Connection cross section : 0.2...6 mm² single core (AWG 24...9); 0.2...4 mm² multiple core (AWG 24...11); Climatic category : 25/085/21 (EN 60068-1); Test isolation voltage : 2.7 kV (L - N), 2 s; 2.1 kV (L - L), 2 s (EN 60939-2); Connection : Screw connection, touch protected; Mounting method : DIN-rail mountable TH35 (EN 60715); Functional description : The single phase 2-stage EMC filters MEF 1/2 are used in the range 0.1...30 MHz to suppress cable carried interference on mains and control cables. The best filter performance is achieved by using short connection wires (suggestion: earth connection < 10; Application : asymmetrical interferences: - units with high switching frequency and repetition, - switch mode P.S.U.s, - in DC mains, - in front of transformers, - for frequency inverters; eClass : 27130806; Packaging unit : 1

Customs tariff number
85363010
Weight
0.45 kg
Dimensions
107×65×39 mm
EAN
4048879029315